The U.S. Cybersecurity and Infrastructure Security Agency (CISA) published three ICS (industrial control systems) advisories this week covering hardware from Danfoss AK-SM 8xxA Series, Schneider Electric EcoStruxure Power Build Rapsody software, and AutomationDirect C-More EA9 Programming Software. Typically, this equipment is deployed across global critical infrastructure sectors, covering commercial facilities, energy, critical manufacturing, and water and wastewater systems.
In an advisory, CISA has flagged a critical stack-based buffer overflow flaw (CVE-2026-129713, CVSS v3 9.8) in Danfoss AK-SM 8xxA Series devices running version 5.4.0 or earlier. “Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code with webserver privileges.”
The agency added that a stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart, and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability.
Carlo Meijer of Midnight Blue reported CVE-2026-129713 to CISA. This vulnerability will be addressed in an upcoming Danfoss AK-SM 800A Series software release (version 5.5.x). In addition, Danfoss will remove the ability for users to disable Strict Mode in future software releases.
Until a software update is available, Danfoss recommends that asset owners and operators follow the guidance provided in the product documentation and do not expose devices directly to the Internet or assign them public IP addresses; restrict remote access to affected devices by using a secure VPN or other protected network architecture; configure affected devices to operate in Strict Mode, which provides enhanced security protections; and use strong, unique passwords for all user accounts and administrative access.
In another advisory, CISA detailed a vulnerability in Schneider Electric’s EcoStruxure Power Build Rapsody, software used to enter or import single-line diagrams and generate an extensive bill of materials for a switchboard, covering all devices, connection items, and mounting components. Affecting the global energy, critical manufacturing, and commercial facilities sectors, the flaw is a use-after-free vulnerability (CWE-416), tracked as CVE-2026-119055 and carrying a CVSS v3 score of 5.3. A local attacker could exploit it by tricking an end user into opening a specially crafted malicious SSD file, potentially achieving arbitrary code execution. Left unremediated, it could also cause memory corruption and heap- or stack-based buffer overflows.
Schneider Electric CPCERT reported this vulnerability to CISA. Eight language-specific builds are affected: French (2.9.1.0 and earlier), Spanish (2.8.5.0301 and earlier), Portuguese (2.8.7.0101 and earlier), Belgian French (2.8.8.0201 and earlier), Belgian English (2.8.3.0201 and earlier), International English (2.8.4.0401 and earlier), International French (2.8.6.0000 and earlier), and Dutch (2.8.2.0000 and earlier).
Schneider Electric has released a vendor fix, available through its website. The patched versions are French 2.9.12.0101, Spanish 2.9.5.0000, Portuguese 2.9.7.0000, Belgian French 2.9.8.0000, Belgian English 2.9.3.0000, International English 2.9.4.0000, International French 2.9.6.0000, and Dutch 2.9.6.0000.
In another advisory, CISA identified a heap-based buffer overflow vulnerability in AutomationDirect’s C-More EA9 Programming Software. Tracked as CVE-2026-127280, the flaw carries a CVSS v3 score of 7.8 and affects version 6.80 and earlier. AutomationDirect has released a vendor fix. Users should update the software to version 6.81, available through the company’s software downloads page.
C-More EA9 Programming Software V6.80 does not adequately validate data read from a project file before using it in heap memory operations. A crafted file causes a heap buffer overrun during file open, resulting in heap corruption and instability within the application. An attacker can exploit this vulnerability by convincing a user to open a malicious project file delivered through common distribution channels such as email, file sharing, or removable media. “Successful exploitation of this vulnerability could allow attackers to corrupt application memory and cause instability or a crash, potentially leading to arbitrary code execution, if a user is convinced to open a malicious file.”
rgod of TrendAI Zero Day Initiative reported this vulnerability to CISA.
Deployed across the global critical manufacturing, energy, and water and wastewater sectors, the affected products come with a clear message from the advisory: asset owners and operators who cannot update to the latest software or firmware right away should apply compensating controls to reduce risk until the update can be performed. These measures are temporary and do not replace the update, which remains the primary recommended remediation. They should be applied as appropriate to the vulnerability, the assessed risk, operational requirements, and the characteristics of each environment, and implemented under the established management-of-change process. Before making any isolation, access-control, or network-configuration changes, organizations should evaluate the potential impact on safety, availability, and essential operational functions.
On the network side, the advisory calls for isolating affected engineering workstations and OT systems from external and nonessential networks, including the internet and corporate IT networks, where operationally feasible. Vendor, contractor, and other remote access to the affected OT environment should be disabled or tightly restricted until the vulnerability is remediated.
Where remote access is operationally required, organizations should use a hardened jump host, enforce multi-factor authentication, apply least-privilege access, and limit connections to authorized, time-bound sessions. Device communication should run over trusted, dedicated OT networks, and higher-criticality systems may warrant dedicated or physically separated infrastructure where practicable. Where logical segmentation is used, the controls should be properly configured, secured, and monitored.
Access to the affected systems should be limited, both physically and logically, to authorized personnel, with least-privilege principles applied to administrative, engineering, maintenance, and service access. On the host side, application allowlisting should be configured where supported so that only trusted, pre-approved applications can run and unauthorized software is blocked. Antivirus or endpoint detection and response (EDR) tools should be used where supported and compatible, and host-based and network firewalls should permit only required communications. Unnecessary services, ports, protocols, and communication pathways should be disabled. Where a service or protocol cannot be turned off for operational reasons, access should be restricted to trusted systems and authorized users wherever possible.
Visibility and recovery matter as well. System, security, and network logs should be enabled and reviewed regularly to spot suspicious or unauthorized activity, and communications to and from affected systems should be monitored for unexpected connections or shifts in network behavior where appropriate. Organizations should keep secure, tested, and preferably offline backups of PLC programs, device configurations, engineering workstation configurations, and any other information needed to restore operations, and should periodically confirm that those backups can actually be restored.
Critical OT functions should also be able to keep running without unnecessary dependencies on external networks, cloud services, remote-access services, corporate IT services, or other nonessential systems. If removable media is needed to move files into an isolated or restricted environment, it should be controlled and trusted, and scanned for malicious content before use.
The advisory also urges continuous evaluation of the risks of running vulnerable or outdated firmware or software, with compensating controls adjusted as the threat environment, operational requirements, or available vulnerability information changes. These controls are meant to reduce exposure while remediation is pending, and organizations should prioritize applying the vendor-provided update as soon as it can be safely tested and deployed in the operational environment.
CISA is urging users to take defensive measures to reduce the risk of exploitation, starting with limiting network exposure so that no control system device or system is accessible from the internet. Control system networks and remote devices should sit behind firewalls, isolated from business networks. Where remote access is unavoidable, the agency advises more secure methods such as Virtual Private Networks (VPNs), while cautioning that VPNs can carry vulnerabilities of their own and should be updated to the latest version. A VPN is also only as secure as the devices connected through it.
CISA reminded organizations to conduct a proper impact analysis and risk assessment before deploying any defensive measures. Its control systems security recommended practices section on the ICS webpage offers several cyber defense products for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. The agency also encourages organizations to adopt its recommended strategies to defend ICS assets proactively. Further mitigation guidance appears in the technical information paper ICS-TIP-12-146-01B, Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations that observe suspected malicious activity should follow their internal procedures and report findings to CISA, which tracks and correlates them against other incidents.
To guard against social engineering, CISA also advises users not to click links or open attachments in unsolicited emails, and points to its guidance on recognizing and avoiding email scams, phishing, and social engineering attacks.
CISA noted that no known public exploitation specifically targeting these vulnerabilities has been reported to the agency so far.